PTB 14 ATEX 2009
IECEx PTB 14.0033
UL-BR 15.0323
KCS KTL 16-KA4BO-0399 (Gas)
KCS KTL 16-KA4BO-0400 (Dust)
ATEX:
II 2(1) G Ex ib [ia IIC/IIB Ga] IIC T4 Gb
II (1) D [Ex ia Da] IIIC
IECEx:
Ex ib [ia IIC/IIB Ga] IIC T4 Gb
[Ex ia Da] IIIC
-20 °C to +60 °C
The ANTARES 8TC Remote I/O Module (8 thermocouples) is suitable for the intrinsically safe connection of a variety of thermocouple types. All of the I/O module’s transmission channels are conductively connected to each other. The ANTARES 8TC Remote I/O Module is operated by and supplied with power through the ANTARES Rail Control Unit (RCU). A bus rail is not necessary. Hot-swap capability allows the electronic unit to be replaced without disconnecting from voltage even in a potentially explosive atmosphere. Parameters can be set for every channel. Line break/short-circuit monitoring can be programmed for each channel. See the system description for installation instructions.
Protection class | (EN 60529) Enclosure: IP 30 in the ANTARES system construction |
Dimensions | (W x H x D) 45 mm x 110 mm x 114.5 mm |
Material | Enclosure material: PA |
Installation | Mounting rail TH 35-15 DIN EN 60715 (Metal) |
Storage temperature | -25 °C up to +85 °C |
Humidity | 5 up to 95 %, non-condensing |
Vibration | (EN 60068-2-6) 2 g/7 mm; 5 Hz up to 200 Hz into all 3 axes |
Shock resistance | (EN 60068-2-27) 15 g/11 ms, ± 3 shocks per direction |
Weight | approx. 380 g |
Measurement range | -80 mV to +80 mV |
Interface | Number of channels 8 inputs Ex i (short-circuit proof) |
Voltage | Supply voltage: through internal bus |
Connection | - plug-in tension spring clamp 4-pole - up to 2.5 mm² - optional coding and numbering |
*Refer to the documentation for more detailed information