PTB 11 ATEX 2018
IECEx PTB 11.0061
DNV A-13339
TC RU C-DE.BH02.B.00005
KCS KTL 13-KB4BO-0302
KCS KTL 13-KB4BO-0303
UL BR 13.0260
ATEX:
II 2(1)G Ex ib [ia IIC/IIB Ga] IIC T4 Gb
II (1)D [Ex ia Da] IIIC
IECEx:
Ex ib [ia IIC/IIB Ga] IIC T4 Gb
[Ex ia Da] IIIC
-20 °C up to +60 °C
The Remote I/O Module ANTARES 4AIO is operated and supplied with power by means of the Rail Control Unit (RCU) ANTARES. This module allows the direct linking of 4 intrinsically safe 2-, 3-, 4-conductor transmitters or the output of 0 up to 20 mA or 4 up to 20 mA signals.
The hot-swap capability allows the electronic unit to be replaced without disconnecting from voltage even in an Ex atmosphere. The internal and galvanically isolated bus connection is established by simply joining the modules to the RCU. A bus rail is not necessary. Line break/short-circuit monitoring can be programmed for each channel. The bus status messages and individual messages per channel are displayed through the LEDs. This facilitates diagnosis at the module as well. The ANTARES Designer software allows parameters to be set for the signal range, channel type (in or out) and a 4-stage input filter for each channel. See the system description for installation instructions.
Protection class | (EN 60529) Enclosure: IP 30 in the ANTARES system construction |
Dimensions | (W x H x D) 45 mm x 110 mm x 114.5 mm |
Material | Enclosure material: PA |
Installation | Mounting rail TH 35-15 DIN EN 60715 (Metal, galvanized steel) |
Storage temperature | -25 °C up to +85 °C |
Humidity | 5 up to 95 %, non-condensing |
Vibration | (EN 60068-2-6) 2 g/7 mm; 5 Hz up to 200 Hz into all 3 axes |
Shock resistance | (EN 60068-2-27) 15 g/11 ms, ± 3 shocks per direction |
Weight | approx. 390 g |
Display | LEDs in enclosure front: Status ST, PWR, ERR1, ERR2 Inputs/Outputs 2 LEDs per channel 1 x LED gelb channel setting 1 x LED rot channel error |
Interface | Number of channels 4 inputs or outputs Ex i (short-circuit-proof) Inputs active/passive |
Voltage | Minimum voltage at 20 mA: 16 V |
Resistance | Input resistance: Ri = 10 Ohm |
Signal range | 0 to 20 mA or 4 to 20 mA |
Connection | - plug-in tension spring clamp 4-pole - up to 2.5 mm² - optional coding and numbering |
*Refer to the documentation for more detailed information